Infineon and Megmeet develop 800V DC power systems

Infineon and Megmeet develop 800V DC power systems

Infineon and Megmeet are extending their collaboration on 800V direct current infrastructure for AI data centres, with a new three-phase power shelf using second-generation silicon carbide switching devices.

Infineon and Megmeet develop 800V DC power systems
Summary
  • Megmeet has developed a three-phase AI power shelf incorporating Infineon's CoolSiC MOSFET G2 technology.
  • The collaboration also covers server power supplies, intermediate bus converters, and solid-state transformers for future 800V DC architectures.
  • The manufacturers claim efficiency exceeding the peak 80 PLUS Ruby requirements, but have not supplied independent certification or complete measurement results.

German semiconductor manufacturer Infineon Technologies is expanding its collaboration with Shenzhen Megmeet Electrical to develop power conversion equipment for 800V direct current architectures used in high-density AI data centres.

The companies announced on 19 November that Megmeet had developed a three-phase power shelf incorporating Infineon’s second-generation CoolSiC silicon carbide MOSFET technology.

The collaboration also covers server power supply units, intermediate bus converters, and solid-state transformers, extending their existing relationship across several components of data centre electrical infrastructure.

The latest power shelf is intended to support the increasing electrical demands of AI computing installations, where processors, memory, networking, and other equipment must operate reliably under substantial and changing power loads.

Infineon and Megmeet say the design achieves system efficiency above the peak efficiency requirements associated with the 80 PLUS Ruby specification.

That comparison is a manufacturer claim. The announcement does not disclose a complete set of measured efficiency figures, the applicable test conditions, or independent certification of the finished equipment.

The distinction between claimed performance and verified operating results is important when evaluating the contribution of a new power conversion design to an entire data centre.

Computing installations receive electricity through a series of distribution and conversion stages. At each stage, equipment must regulate voltage, maintain suitable operating conditions, and limit electrical losses.

Although power electronics can operate with high efficiency, even relatively small conversion losses become substantial where equipment is supplying large computing loads continuously.

A power conversion system that loses 2% of a 1MW electrical input dissipates approximately 20kW as heat. That heat must be removed through the equipment’s own cooling arrangements and ultimately through the facility’s thermal infrastructure.

Reducing conversion losses can therefore lower both the electricity required to supply computing equipment and the heat that must be rejected by the surrounding installation.

The benefit depends on the performance of the complete electrical architecture rather than a single semiconductor component.

Infineon’s CoolSiC MOSFET G2 devices use silicon carbide, a semiconductor material suited to power electronics operating at comparatively high voltages and switching speeds.

Suitable silicon carbide devices can reduce switching and conduction losses compared with alternative designs, although the result depends on the selected components, circuit arrangement, switching frequency, cooling, and operating load.

Infineon says the devices incorporate its .XT interconnection technology to reduce thermal resistance and improve heat dissipation.

Thermal resistance influences the temperature difference between the semiconductor junction and its surrounding cooling system. Lower resistance can help control device temperatures when electrical losses generate heat within the component.

Maintaining appropriate operating temperatures can support equipment reliability, particularly where power conversion systems must sustain high loads over extended periods.

Megmeet is using the devices in its three-phase power shelf, integrating semiconductor switching with the other components required to convert and regulate electricity for computing equipment.

Three-phase input arrangements can support substantial power transfer, while the downstream conversion equipment must supply the voltage and current characteristics required by the connected system.

The 800V DC architecture being developed through the collaboration addresses a separate issue: distributing increasing amounts of electrical power without allowing conductor currents to rise excessively.

For a given electrical power, increasing the distribution voltage reduces the current required. Electrical losses in conductors are related to the square of the current, making current reduction relevant to the design of cables, busbars, connectors, and distribution equipment.

Higher-voltage distribution may reduce certain conductor requirements and losses, but it also introduces protection and maintenance challenges that must be addressed through the complete design.

Direct current does not naturally cross zero during each electrical cycle in the same way as alternating current. Switching and interrupting DC faults therefore requires equipment designed for the resulting electrical stresses.

Appropriate isolation, fault detection, protective devices, and operating procedures are essential when higher-voltage DC systems are introduced into computing facilities.

The use of 800V distribution also does not mean that every processor or server component operates at that voltage.

Power must still be converted into the lower voltages required by the computing equipment. Intermediate bus converters and subsequent regulation stages provide part of that function.

Reducing unnecessary conversion stages and improving efficiency at the remaining stages can affect the energy required to supply high-density racks, provided the architecture maintains suitable voltage regulation and electrical protection.

The companies’ collaboration includes intermediate bus converters and solid-state transformers, but the announcement does not establish that every component is commercially available or has been installed as part of one complete operating system.

Solid-state transformers use power electronic conversion to perform functions associated with voltage transformation and electrical control. Their practical integration depends on the voltage levels, protection arrangements, efficiency requirements, and interfaces used within the wider installation.

Dynamic computing loads create another design consideration. AI accelerators can change their electrical demand as workloads vary, requiring power systems to respond without allowing unacceptable voltage disturbances to reach sensitive equipment.

Infineon says its silicon carbide devices can support more stable power delivery under rapidly changing loads. The claim is consistent with the intended role of fast-switching power electronics, but no independently measured transient response data for the complete Megmeet design was supplied.

Equipment performance must ultimately be evaluated under the load changes, thermal conditions, and operating limits expected in the intended deployment.

The new collaboration builds on earlier work between the manufacturers. Megmeet has previously used Infineon’s CoolMOS 8 and OptiMOS 6 devices in single-phase AI server power supply platforms.

The move towards three-phase power conversion and higher-voltage DC infrastructure extends that relationship into systems intended for larger aggregate electrical loads.

Infineon is also working with other companies on related power distribution technologies. Its previously reported collaboration with Eaton concerns solid-state transformer development, whereas the Megmeet announcement includes a new three-phase power shelf and additional conversion components.

The two programmes involve different equipment and partners and should not be treated as the same previously announced product.

No named European data centre installation, commercial deployment date, or complete independent performance report for the Megmeet power shelf was disclosed in the 19 November announcement.

The development therefore concerns power conversion equipment being prepared for future computing infrastructure rather than confirmation that an 800V system has been commissioned at a particular facility.

Subsequent technical specifications, certification information, and operating results will establish how the proposed improvements translate into measurable efficiency, electrical performance, and maintenance requirements within completed data centre installations.