Summary
- Vertiv's 800V DC portfolio now supports rack, compute pod, and data hall distribution architectures.
- New equipment includes the 1.5MW PowerDirect 9000 and 5MW PowerNexus MV SST.
- The architectures combine power conversion, energy storage, distribution, protection, and controls to support high-density computing loads.
Vertiv has expanded its 800V direct current (DC) electrical infrastructure portfolio with systems capable of supplying entire compute pods and data halls, extending an architecture originally introduced at rack level in May.
The expanded portfolio, detailed in the company’s UK communications on 25 November following its international unveiling earlier this month, allows operators to introduce DC distribution at different points within a facility’s electrical infrastructure.
Existing buildings can retain upstream alternating current (AC) distribution while introducing DC conversion beside individual racks or groups of computing systems. Purpose-built facilities can instead incorporate direct conversion from medium-voltage AC to an 800V DC distribution network serving multiple data halls or computing pods.
Increasing the distribution voltage reduces the current required to deliver a given amount of electrical power. At higher computing densities, that can influence conductor sizing, distribution equipment requirements, and resistive electrical losses.
Moving power conversion outside computing racks can also release space for additional hardware, although the amount of equipment a facility can accommodate remains dependent on its electricity supply, cooling infrastructure, and network architecture.
Scott Armul, chief product and technology officer at Vertiv, said: “The 800 VDC power train is not just a new power product or conversion methodology; it is a set of architectures and system designs.”
Shared conversion supports megawatt-scale computing pods
Vertiv’s existing PowerDirect 5000 uses a separate power rack positioned beside computing equipment, accepting a 480V AC supply and converting it to 800V DC or a bipolar ±400V DC configuration.
The system is configurable to 800kW and accommodates 30 hot-pluggable power supply units, each rated at 30kW. An integrated battery backup unit is designed to provide at least 50 seconds of electrical support.
Within the computing rack, the PowerDirect 3000 converts the higher distribution voltage to 54V DC for individual computing trays. The 90kW power shelf occupies a single rack unit and has a manufacturer-rated peak conversion efficiency of up to 98.5%.
The shelf also supports a short power pulse equivalent to 180% of its rated output for 0.5 milliseconds, allowing it to accommodate rapid fluctuations in demand associated with accelerator-based computing.
Vertiv estimates that relocating power conversion and energy storage into a separate enclosure can release between eight and 16 rack units for computing equipment. Retaining upstream AC infrastructure allows the approach to be considered for existing facilities and mixed AC and DC installations.
The new PowerDirect 9000 moves conversion further upstream, consolidating the supply to a row of racks or compute pod within a 1.5MW power centre.
Its capacity can be increased in 60kW increments, with electricity distributed through a DC busway and tap-off equipment to the power shelves within individual racks.
EnergyCore Li5 battery cabinets connect directly to the DC bus. Each provides up to 200kW of continuous backup power, with Vertiv specifying conversion efficiency of up to 98% and support for six cabinets operating in parallel through active current sharing.
Consolidating conversion and backup equipment can reduce the number of separate power enclosures required across a computing installation. Shared infrastructure also increases the importance of fault isolation and redundancy design because an interruption at the common supply point could affect multiple racks.
Medium-voltage conversion moves outside the data hall
Vertiv’s new PowerNexus MV SST solid-state transformer extends the distribution architecture towards the incoming electricity supply.
The 5MW system converts medium-voltage AC directly to 800V DC through a single system-level conversion stage, removing between two and three intermediate conversion stages found in conventional electrical architectures, according to the manufacturer.
Its containerised, liquid-cooled configuration is designed for outdoor installation and provides galvanic isolation between the input and output. Vertiv specifies AC-to-DC efficiency of up to 98%, with a single unit capable of supporting a 4.8MW super pod reference architecture.
External energy storage can be connected through a DC-to-DC converter to support fault ride-through and manage rapid changes in computing demand. Bidirectional power flow provides further opportunities for active power support, subject to compatible network connection arrangements.
The system complements Vertiv’s previously introduced medium-voltage UPS architecture, although the solid-state transformer addresses a different stage of electrical conversion and distribution.
Higher-voltage DC installations require protection and maintenance procedures appropriate to their electrical characteristics. Unlike alternating current, direct current does not have natural periodic zero crossings that can assist in interrupting electrical arcs.
Vertiv’s portfolio incorporates protected busbars, high-voltage isolation, midpoint grounding, and ground-fault detection, alongside service arrangements developed for DC equipment.
Pilot programmes and technical validation activities remain underway. The three architectures allow operators to assess where higher-voltage distribution could be introduced within existing or proposed facilities, with the resulting electrical performance dependent on equipment selection, system configuration, and the characteristics of the computing workloads being supplied.